Product Overview


A rack/tower UPS with double-conversion topology, the CyberPower Smart App Online OL2000RMXL2U provides sine wave output to mission-critical applications and equipment requiring seamless power protection. This model comes with an LCD front panel, audible alarms, and a resettable circuit breaker. The OL2000RMXL2U offers generator compatibility and delivers clean AC power with zero transfer time. This model can use up to four ABP72VRM2U Extended Battery Modules for expanded runtime and faster restoration of full backup power. The OL2000RMXL2U comes with a three-year warranty and a $400,000 Connected Equipment Guarantee.

NOTE: This model requires a 20A outlet.

  • Double-Conversion Topology
    Provides consistent, clean, and nearly perfect power, regardless of the condition of incoming power. Systems with this technology operate on isolated DC power 100% of the time and have a zero transfer time because they never need to switch to battery. Double-Conversion UPS systems are designed for high-end system components, corporate servers, lab equipment, and other sensitive electronic devices.
  • Sine Wave
    The UPS generates energy that is identical to, or cleaner than, the utility company's power grid. Benefits include low total harmonic distortion, minimal electrical noise, and optimal line clarity.
  • Microprocessor-Based Digital Control
    Digital routing is maintained through a network of integrated circuitry and discrete values used for internal system processing, which significantly increases its efficiency and responsiveness.
  • RM/T Configuration
    The OL Series can be set up in a Tower, or in a Rackmount (2U) form.
  • Extended Battery Module (EBM)
    Extends runtime by adding EBMs. Models vary in the number of EBMs which can be added.
  • Dual PC Support
    The model has two communication ports that allow the user full control of dual PCs or servers.
  • LED Front Panel
    Immediate system information: load capacity, battery capacity, fault status, and bypass status.
  • PowerPanel® Business Edition Software
    Provides IT professionals with tools for monitoring and managing the UPS and backup power. This software offers remote management functionality. Free software download available. See the Resources tab.
  • Metal Housing
    Rigid metal construction allows for placement in areas with a demanding environment.
  • Audible Alarms
    Identify when the model is running on battery power, overloaded, or has a low battery.
  • Resettable Circuit Breaker
    Interrupts an electric current in a circuit when the current becomes too high.
  • Three-Year Warranty
    CyberPower will repair or replace a defective UPS system (including batteries) within three years of the purchase date. See warranty for details.
  • Connected Equipment Guarantee
    CyberPower will repair or replace properly connected equipment if it is damaged by a power surge.
OL2000RMXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
General  
UPS Topology Double-Conversion
Input  
Voltage 60Vac - 142Vac
Phase Single
Frequency 40Hz - 70Hz
Power Factor .95 @ full load
Plug Type NEMA 5-20P
Plug Style Straight
Cord Length 6'
Output  
VA 2,000
Watts 1,400
Automatic Voltage Regulation No
On Battery Voltage 110Vac / 120Vac / 127Vac +/- 3%
On Battery Frequency 50/60Hz ± .5%
On Battery Waveform Sine Wave
Outlet Type NEMA 5-20R, NEMA L5-20R
Outlets - Battery & Surge Protected 5
Voltage T.H.D. 4% max @ full linear load, 6% @ full RCD load
Crest Factor 3:1
Overload Protection Internal circuitry limiting / circuit breaker
Transfer Time 0ms
Battery  
Runtime at Half Load (min) 19
Runtime at Full Load (min) 8
Battery Type Sealed Lead-Acid
Battery Size 12V/7AH
Replacement Battery RB1270X6PS
Battery Quantity (x4 or x8)
User Replaceable Yes
Typical Recharge Time 3 Hours (90% charged)
Extended Runtimes Available Yes, with optional ABP72VRM2U Battery Pack
Surge Protection & Filtering  
Surge Suppression 736 Joules
Management & Communications  
USB Port Yes
HID Compliant USB Port No
Serial Port Yes
Emergency Power Off (EPO) Port Yes
Cable Management USB Cable
LED Indicators Power On, Battery, Inverter, Bypass, Critical Outlet 1, Critical Outlet 2, Wiring Fault, Battery Alarm, Overload, Load
Audible Alarms Input Fault, Battery Fault, Low Battery, Overload
Software PowerPanel® Business Edition
SNMP / HTTP Remote Monitoring Yes, with optional RMCARD301
AS400 Management Yes, with optional COMMCARD300
Physical  
Rack Size 2U
Form Factor Rack/Tower
Dimensions - W×H×D (in) 17.25 × 3.5 × 26 inches
Weight (lbs) 70.0 lbs
Environmental  
Operating Temperature 32 °F to 95 °F / 0 °C to 35 °C
Operating Humidity 0% - 95% non-condensing
Audible Noise At 1m < 47 dBA
Certifications  
Safety UL1449
Environmental RoHS Compliant
Warranty  
Product Warranty 3 Years Limited
Connected Equipment Guarantee Lifetime
CEG Amount $400,000
OL2000RMXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
Higher Capacity UPS for Longer Runtimes

To determine the size of the UPS that you need, identify the total power load (measure in VA/Watts) of the connected equipment, along with the amount of runtime required (in minutes). Also, think about any equipment that might be connected to the UPS in the future, which could affect the calculations for load and runtime.

Estimating expected UPS runtimes can be challenging, particularly when the consistency of the utility power is not well known. Selecting a UPS with a load capacity 30-35% above the required power load offers the advantage of longer runtimes. This can lower the risk of overloading the UPS and causing an unnecessary UPS shutdown.

Although the initial outlay of a UPS increases with its size because of the higher capacity required for components, long-term operating costs typically decrease. When a UPS operates below maximum capacity, it reduces the stress on components. Sizing a UPS to run loads significantly lower than its capacity also increases spare capacity for future growth, along with extending runtimes.


Efficient Remote Management

The Smart App Series offers full-featured network UPS management capabilities with the PowerPanel® Business Edition software and an optional SNMP network management card. These remote management tools enable centralized power management, monitoring, control, and configuration. They also provide for safe shutdown of connected servers, workstations, and other devices via a standard Web browser or network management system (NMS).

Safe Shutdown

The PowerPanel® Business Edition software, included with every Smart App Sinewave UPS, enables an administrator to remotely manage each aspect of the UPS and facilitate the orderly automatic shutdown of connected equipment in the event of an extended power outage. This software also provides comprehensive network power management for corporate servers and critical workstations supported by the UPS, such as application/operating system shutdown, event logging, reporting, alerts and notifications.

Programmable Outlet Control

Smart App UPS systems allow programming of critical outlets and non-critical outlets, giving administrators the ability to prioritize outlets and increase battery backup runtimes for the most critical equipment during extended power outages. Programmable outlet control also gives an administrator the option to delay-start non-critical outlets, permitting the internal batteries to fully recharge more quickly. This feature is vital to data centers where seamless, uninterrupted equipment bootup is a necessity.


Sine Wave Power

In the U.S., utility companies provide power to households and offices by distributing single phase alternating current (AC) power at a frequency of 60 Hz. Electrical power can be graphically depicted as a sine wave whereby the electrical signal alternates from +120 volts to -120 volts at a rate of 60 times per second (60 Hz). To enable more efficient operation of large, heavy equipment, utility companies provide commercial and industrial locations with three phase AC power which consists of three overlapping sine waves offset by 120 degrees.

Although utility companies strive to distribute 100% sine wave power, many factors can introduce electrical noise into the AC power signal in the form of sine wave distortions and as voltage sags, surges, spikes, or other irregularities. Sine wave power is important for the optimal functioning of sensitive desktop computers and related peripheral equipment. Without sine wave power output, microprocessor-based equipment can become inoperative or sustain damage from power signal distortions.

OL2000RMXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
OL2000RMXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
OL2000RMXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
Model Output VA Output Watts Outlets MSRP
OL1000RTXL2U 1000 VA 900 W 8 NEMA 5-15R $645.00
OL1500RTXL2U 1500 VA 1350 W 8 NEMA 5-15R $815.00
OL1500RTXL2UN 1500 VA 1350 W 8 NEMA 5-15R $995.00
OL2200RTXL2U 2200 VA 1800 W 6 NEMA 5-20R
1 NEMA L5-20R
$1165.00
OL3000RTXL2U 3000 VA 2700 W 6 NEMA 5-20R
1 NEMA L5-30R
$1425.00
OL3000RTXL2UHV 3000 VA 2700 W 2 NEMA L6-20R
1 NEMA L6-30R
$1675.00
OL6000RT3U 6000 VA 5400 W 2 NEMA L6-30R
2 NEMA L6-20R
$3545.00
OL8000RT3U 8000 VA 7200 W 3 NEMA L6-30R
1 Hardwire Terminal Block
$4395.00
OL10000RT3U 10000 VA 9000 W 3 NEMA L6-30R
1 Hardwire Terminal Block
$5320.00
OL6000RT3UTF 6000 VA 5400 W 6 NEMA 5-20R
2 NEMA L6-20R
1 NEMA L6-30R
1 Hardwire Terminal Block
$4695.00
OL8000RT3UTF 8000 VA 7200 W 12 NEMA 5-20R
4 NEMA L6-30R
2 NEMA L6-20R
1 Hardwire Terminal Block
$5695.00
OL10000RT3UTF 10000 VA 9000 W 12 NEMA 5-20R
4 NEMA L6-30R
2 NEMA L6-20R
1 Hardwire Terminal Block
$6595.00
OL6000RT3UPDU 6000 VA 5400 W 2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$3795.00
OL8000RT3UPDU 8000 VA 7200 W 2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$4595.00
OL10000RT3UPDU 10000 VA 9000 W 2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$5455.00
OL6000RT3UPDUTF 6000 VA 5400 W 6 NEMA 5-20R
2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$4695.00
OL8000RT3UPDUTF 8000 VA 7200 W 6 NEMA 5-20R
2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$5895.00
OL10000RT3UPDUTF 10000 VA 9000 W 6 NEMA 5-20R
2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$6755.00
OL6KRT3UHW 6000 VA 5400 W 1 Hardwire Terminal Block $2995.00
OL8KRT3UHW 8000 VA 7200 W 1 Hardwire Terminal Block $4455.00
OL10KRT3UHW 10000 VA 9000 W 1 Hardwire Terminal Block $4695.00
Ask a CyberPower tech support representative to contact you.



CyberPower Systems values your privacy and your information will never be rented or sold. Information provided will be used for CyberPower's internal use only. View our Privacy Policy.

Please enter the username or email associated with your My CyberPower account.


Thank you! You should receive an email shortly with information on how to change your password.


CyberPower Systems values your privacy and your information will never be rented or sold. Information provided will be used for CyberPower's internal use only. View our Privacy Policy.

Thank you for submitting your information. A CyberPower representative will get in contact with you shortly.


An error has occurred while you were attempting to submit this form - please try again. If the problem persists, please call our sales hotline at 1 (877) 297-6937. Thank you!