OL2200RTXL2U

Smart App Online UPS Series


OL2200RTXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection

Product Overview


A rack/tower UPS with double-conversion topology, the CyberPower Smart App Online OL2200RTXL2U provides sine wave output to mission-critical applications and equipment requiring seamless power protection. This model comes with an extendable LCD control panel, Smart Battery Management charging design, Fast Charge Technology, and energy-saving GreenPower UPS™ ECO Mode. The OL2200RTXL2U offers generator compatibility and delivers clean AC power with zero transfer time. With the BP72V60ART2U Extended Battery Module for expanded runtime and faster restoration of full backup power. The OL2200RTXL2U comes with a three-year warranty and a $400,000 Connected Equipment Guarantee.

  • Data Line Protection
    Prevents power surges that travel through telephone and Ethernet lines from causing damage to electronics.
  • Double-Conversion Topology
    Provides consistent, clean, and nearly perfect power, regardless of the condition of incoming power. Systems with this technology operate on isolated DC power 100% of the time and have a zero transfer time because they never need to switch to battery. Double-conversion UPS systems are designed for high-end system components, corporate servers, lab equipment, and other sensitive electronic devices.
  • Sine Wave Output
    Provides power protection to ENERGY STAR® 6.0 systems with Active PFC power supplies.
  • Extendable LCD Panel
    Displays UPS statuses and customizable operating settings from up to 10 ft. away (with optional cable). The extendable LCD control panel can be configured in English, Spanish, or French for ease of use.
  • Extended Battery Module (EBM)
    Extends runtime by adding EBMs. This UPS allows for up to ten added modules.
  • Fast Charge Technology
    Allows UPS batteries to return to 100% capacity more rapidly by utilizing a built-in charger inside each EBM. Restores a complete charge within 5 hours regardless of the number of EBMs.
  • Smart Battery Management (SBM)
    Improves and extends the functional life of a UPS battery and reduces excessive heat during work cycles by using a three-cycle charging process.
  • GreenPower UPS™ ECO Mode
    Improves UPS efficiency up to 95%; saves on electrical and cooling costs.
  • Hot-Swappable Batteries
    Eliminate downtime related to UPS power maintenance for continuous power availability.
  • Critical & Non-Critical Loads
    The UPS has two banks of outlets which can be configured so that the non-critical loads shut off after a set timeframe to provide additional runtime for the critical load outlet. Users can prioritize their equipment runtimes to maximize the output of the UPS to meet their power requirements.
  • Emergency Power Off (EPO)
    Allows the UPS to be shut off in the event of an emergency, when the EPO port is connected to an EPO switch.
  • Generator Compatible
    Provides stable sine wave output (free of harmonics and distortion) without switching to battery mode when running on generator input power.
  • Converter Mode
    Provides the flexibility to set the output frequency, regardless of the input frequency, to match connected equipment by selecting 50Hz or 60Hz output on the LCD control panel.
  • USB & Serial Connectivity
    Enables full integration with built-in power management and auto shutdown features on Windows, Linux, and VMware systems through a HID-compliant USB port and Serial port.
  • EMI/RFI Filters
    Prevent electromagnetic and radio frequency interference to ensure clean power for connected equipment.
  • Audible Alarms
    Identify when the model is running on battery power, overloaded, or has a low battery.
  • Resettable Circuit Breaker
    Interrupts an electric current in a circuit when the current becomes too high.
  • LED Status Lights
    Indicate Power On, Line Mode, Battery Mode, Bypass Mode, Fault, Replace Battery.
  • Rack/Tower Versatility
    Allows for horizontal rack or vertical tower installation.
  • PowerPanel® Business Edition Software
    Provides IT professionals with tools for monitoring and managing the UPS and backup power. This software offers remote management functionality. Free software download available. See the Resources tab.
  • Cisco Compatible
    This CyberPower UPS system is a Cisco EnergyWise compliant end device.
  • ENERGY STAR
    This model is an ENERGY STAR® certified Uninterruptible Power Supply (UPS) system. ENERGY STAR is the trusted, government-backed symbol for energy-efficient products and practices that help save money and protect the environment.
  • Three-Year Warranty
    CyberPower will repair or replace a defective UPS system (including batteries) within three years of the purchase date. See warranty for details.
  • Connected Equipment Guarantee
    CyberPower will repair or replace properly connected equipment if it is damaged by a power surge.

What's In The Box

UPS System, User Manual, USB Device Cable, Telephone Cable, Serial Cable, Warranty Registration Card, PowerPanel Business Edition Software CD, Rackmount Rails (left & right), 2 Rackmount Ears (stands), 8 Flat Head Screws (M5X8L), 12 Pan Head Screws (M5X12L), 8 Plastic Washers, 10 Screw Hole Dust Covers

OL2200RTXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
General  
UPS Topology Double-Conversion
Energy Saving ECO Mode Efficiency >93%
Input  
Voltage 120 VAC
Input Voltage Range 60 – 69 VAC for 0–60% load

70 – 79 VAC for 0–70% load

80 – 89 VAC for 0–80% load

90 – 95 VAC for 0–90% load

96 – 150 VAC for 0–100% load
Frequency Range 40 – 70 Hz
Input Power Factor 0.99
Cold Start Yes
Plug Type NEMA 5-20P
Cord Length 10 ft
Output  
VA 2,200 VA
Watts 1,800 W
On Battery Voltage 100, 110, 115, 120, 125 VAC (Configurable) ± 2%
On Battery Frequency 50/60 Hz ± 0.25 Hz (auto-sensing or configurable)
On Battery Waveform Sine Wave
Outlet Type NEMA 5-20R (6) , L5-20R (1)
Outlets - Total 7
Rated Power Factor 0.82
Crest Factor 3:1
Harmonic Distortion THD < 3% at Linear Load, < 5% at Non-linear Load
ECO Mode Voltage Regulation ±10%, ±15% (Configurable)
Bypass Internal Bypass (Automatic and Manual)
Overload Protection Line Mode:

105~125% Load for 1 min

126~150% Load for 10 sec


Battery Mode:

105~130% Load for 10 sec

131~150% Load for 2 sec
Transfer Time 0 ms
Battery  
Runtime at Half Load 18 minutes
Runtime at Full Load 6 minutes
Battery Type Sealed Lead-Acid
Battery Size 12V/9Ah
Battery Quantity 6
Hot-Swappable Yes
User Replaceable Yes
Replacement Battery Cartridge RB1290X6A
Replacement Battery Cartridge Quantity 1
Typical Recharge Time 4 hours
Extended Battery Option BP72V60ART2U
Smart Battery Management (SBM) Mode Yes
Surge Protection & Filtering  
Surge Suppression 1,335 J (IEC 61000-4-5 Level 3)
EMI/RFI Filter Yes
Phone / Network Protection RJ11/RJ45 1-In / 1-Out
Management & Communications  
LCD Control Panel 43 different settings or status options via the UPS Status menu,
UPS Setup menu, and run Testing menus.

Refer to the "User Manual" on the "Resources" tab for complete options.
Rotatable LCD Control Panel Option Yes
Removable LCD Control Panel Option Yes - Requires a separate DB26 Cable
HID Compliant USB Port Yes
Serial Port Yes
EPO Port Yes
Dry Contacts Yes
Management Cable USB Cable, Serial Cable
LED Indicators Power On (white)

Line Mode (green)

Battery Mode (yellow)

Bypass Mode (yellow)

Fault (red)

Replace Battery (red)
Audible Alarms Battery Mode

Battery Low

Overload

UPS Fault

Replace Battery
Software PowerPanel® Business Edition
SNMP / HTTP Remote Monitoring Yes, with optional RMCARD302, RMCARD303, RMCARD305
Physical  
Rack Size 2U
Form Factor Rack/Tower
Enclosure Contruction Steel
Mounting Hardware Included
Dimensions - W×H×D (in) 17 × 3.5 × 23.62 inches
Dimensions - W×H×D (mm) 590 × 214.1 × 890 mm
Weight (lbs) 68.0 lbs
Weight (kg) 31 kg
Shipping Dimensions - W×H×D (in) 23.23 × 8.43 × 35.04 inches
Shipping Weight (lbs) 86.9 lbs
Shipping Weight (kg) 39.4 kg
Environmental  
Operating Temperature 32 – 104 °F (0 – 40 °C)
Operating Humidity 0 – 90% (non-condensing)
Operating Elevation 0 – 10,000 ft (0 – 3,000 m)
Storage Temperature -4 – 113 °F (-20 – 45 °C)
Storage Relative Humidity 0 – 95% (non-condensing)
Storage Elevation 0 – 50,000 ft (0 – 15,000 m)
Online Thermal Dissipation 736 BTU/hr
Audible noise at 1.5M from surface of unit < 50 dBA
Certifications  
Safety UL1778

CSA C22.2 NO.107.3-05

FCC DOC Class A
Environmental RoHS Compliant
Warranty  
Product Warranty 3 Years Limited
Connected Equipment Guarantee Lifetime
CEG Amount $400,000
OL2200RTXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
Battery Technology

Fast Charge Technology and Smart Battery Management (SBM) prolong the capacity and life of a UPS battery. This provides greater efficiency and fewer battery replacements.

Fast Charge Technology enables the backup power supply to more quickly return to full capacity (100%) because each Extended Battery Module attached to the UPS uses its own charger. Typical systems share only a single charger for all attached battery modules, which increases the time required to fully restore backup power.

Smart Battery Management (SBM) charges a UPS battery in three phases, extending its functional life. SBM also reduces the heat produced by a UPS battery and reduces battery deterioration.


Extendable LCD Control Panel

Often a UPS is installed in a hard-to-reach area, such as a crowded IT closet, the bottom of a rack, or on the floor. A removable LCD control panel allows for easy access and can be placed up to ten feet away from the UPS when connected by a DB26 cable (sold separately).

Menu Functions

UPS Status displays vital information about the UPS. There are 19 status types, including input and output voltage, battery information, runtime estimates, load data, and more.

LCD Settings Configuration offers customization of the UPS with 38 specific operation parameters including output voltage, sync frequency, alarm settings, and more.

Event Log allows for recording of UPS events with or without PowerPanel® Business Edition management software.

Multi-Language (select models) provides options to display text in English, Spanish, French, or German.

Disable Audible Alarms turns off audible alarms, as needed.

Manual Battery Test enables user to run a UPS system test to ensure proper operation.


Higher Capacity UPS for Longer Runtimes

To determine the size of the UPS that you need, identify the total power load (measure in VA/Watts) of the connected equipment, along with the amount of runtime required (in minutes). Also, think about any equipment that might be connected to the UPS in the future, which could affect the calculations for load and runtime.

Estimating expected UPS runtimes can be challenging, particularly when the consistency of the utility power is not well known. Selecting a UPS with a load capacity 30-35% above the required power load offers the advantage of longer runtimes. This can lower the risk of overloading the UPS and causing an unnecessary UPS shutdown.

Although the initial outlay of a UPS increases with its size because of the higher capacity required for components, long-term operating costs typically decrease. When a UPS operates below maximum capacity, it reduces the stress on components. Sizing a UPS to run loads significantly lower than its capacity also increases spare capacity for future growth, along with extending runtimes.

OL2200RTXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection

Shutdown software supports most Window systems

Shutdown software supports most Linux and XenServer

Shutdown software supports most Linux, XenServer, ESX, ESXi

Shutdown software supports VMWARE vSphere, ESXi 4.1 and later

Shutdown software supports VMWARE vSphere, ESXi 4.1 and later

Shutdown software supports most Mac systems

OL2200RTXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
Can I use my UPS in conjunction with a generator?

CyberPower Smart App Online Series UPS systems include a Generator Mode setting specifically designed to work with generators. With varying loads, the frequency output from generators can be erratic. This erratic output can make it difficult for a UPS without a Generator Mode setting to recognize the input power, causing the UPS to function on battery power only. With Generator Mode, the UPS can automatically adjust to frequency fluctuations and maintain a full charge of the batteries.

OL2200RTXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
Model Output VA Output Watts Outlets MSRP
OL1000RTXL2U 1000 VA 900 W 8 NEMA 5-15R $645.00
OL1500RTXL2U 1500 VA 1350 W 8 NEMA 5-15R $815.00
OL1500RTXL2UN 1500 VA 1350 W 8 NEMA 5-15R $995.00
OL2200RTXL2U 2200 VA 1800 W 6 NEMA 5-20R
1 NEMA L5-20R
$1165.00
OL3000RTXL2U 3000 VA 2700 W 6 NEMA 5-20R
1 NEMA L5-30R
$1425.00
OL3000RTXL2UHV 3000 VA 2700 W 2 NEMA L6-20R
1 NEMA L6-30R
$1675.00
OL6000RT3U 6000 VA 5400 W 2 NEMA L6-30R
2 NEMA L6-20R
$3545.00
OL8000RT3U 8000 VA 7200 W 3 NEMA L6-30R
1 Hardwire Terminal Block
$4395.00
OL10000RT3U 10000 VA 9000 W 3 NEMA L6-30R
1 Hardwire Terminal Block
$5320.00
OL6000RT3UTF 6000 VA 5400 W 6 NEMA 5-20R
2 NEMA L6-20R
1 NEMA L6-30R
1 Hardwire Terminal Block
$4695.00
OL8000RT3UTF 8000 VA 7200 W 12 NEMA 5-20R
4 NEMA L6-30R
2 NEMA L6-20R
1 Hardwire Terminal Block
$5695.00
OL10000RT3UTF 10000 VA 9000 W 12 NEMA 5-20R
4 NEMA L6-30R
2 NEMA L6-20R
1 Hardwire Terminal Block
$6595.00
OL6000RT3UPDU 6000 VA 5400 W 2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$3795.00
OL8000RT3UPDU 8000 VA 7200 W 2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$4595.00
OL10000RT3UPDU 10000 VA 9000 W 2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$5455.00
OL6000RT3UPDUTF 6000 VA 5400 W 6 NEMA 5-20R
2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$4695.00
OL8000RT3UPDUTF 8000 VA 7200 W 6 NEMA 5-20R
2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$5895.00
OL10000RT3UPDUTF 10000 VA 9000 W 6 NEMA 5-20R
2 NEMA L6-20R
4 NEMA L6-30R
1 Hardwire Terminal Block
$6755.00
OL6KRT3UHW 6000 VA 5400 W 1 Hardwire Terminal Block $2995.00
OL8KRT3UHW 8000 VA 7200 W 1 Hardwire Terminal Block $4455.00
OL10KRT3UHW 10000 VA 9000 W 1 Hardwire Terminal Block $4695.00
OL2200RTXL2U | Smart App Online UPS Series
Safeguard mission-critical servers, applications, and network equipment with isolated, double-conversion power protection
Ask a CyberPower tech support representative to contact you.



CyberPower Systems values your privacy and your information will never be rented or sold. Information provided will be used for CyberPower's internal use only. View our Privacy Policy.

Please enter the username or email associated with your My CyberPower account.


Thank you! You should receive an email shortly with information on how to change your password.


CyberPower Systems values your privacy and your information will never be rented or sold. Information provided will be used for CyberPower's internal use only. View our Privacy Policy.

Thank you for submitting your information. A CyberPower representative will get in contact with you shortly.


An error has occurred while you were attempting to submit this form - please try again. If the problem persists, please call our sales hotline at 1 (877) 297-6937. Thank you!